D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 87 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Instant Mains Dropout
%
0
50
0
If the mains phase voltages are outside
limits, but not more than this parameter
(with reference to nominal voltage),
then the genset will run without
releasing the mains contactor. When
the genset is ready to take the load, the
load will be transferred.
If this parameter is set to zero then the
mains contactor is immediately released
at mains failure.
Mains Frequency Low
Limit
%
F-100 F+100
F-10%
If the mains frequency goes under this
limit, it means that the mains are off and
starts the transfer to the genset in
AUTO
mode. The value is defined with
reference to Nominal Frequency.
Mains Frequency High
Limit
%
F-100 F+100 F+10%
If the mains frequency goes over this
limit, it means that the mains are off and
starts the transfer to the genset in
AUTO
mode. The value is defined with
reference to Nominal Frequency.
Mains Frequency Fail
Timer
sec
0
10
1
If the mains frequency goes outside of
the limits during this timer, it means that
the mains are off and starts the transfer
to the genset in
AUTO
mode.
Genset Low Voltage
Warning Limit
%
V-100 V+100
V-15%
If one of the genset phase voltages goes
under this limit when feeding the load,
this will generate a
GENSET LOW
VOLTAGE
warning.
Genset Low Voltage
Shutdown Limit
%
V-100 V+100
V-20%
If one of the genset phase voltages goes
under this limit when feeding the load,
this will generate a
GENSET LOW
VOLTAGE
shutdown alarm and the
engine will stop.
Genset High Voltage
Warning Limit
%
V-100 V+100 V+15%
If one of the genset phase voltages goes
over this limit when feeding the load, this
will generate a
GENSET HIGH
VOLTAGE
warning.
Genset High Voltage
Shutdown Limit
%
V-100 V+100 V+20%
If one of the genset phase voltages goes
over this limit when feeding the load, this
will generate a
GENSET HIGH
VOLTAGE
shutdown alarm and the
engine will stop.
Genset Voltage Fail
Timer
sec
0
10
1
If at least one of the genset phase
voltages goes outside of the limits
during this timer, a genset voltage fault
will occur.
16.2. ELECTRICAL PARAMETERS GROUP (continued)
Summary of Contents for D-500
Page 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Page 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Page 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Page 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...