D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 82 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
SMS on Mains Change
-
0
1
0
This parameter controls SMS sending
when mains voltages status is changed.
No warnings generated.
0:
no SMS on mains failed or restored
1:
SMS sent on mains failed or restored
SMS on IP Change
-
0
1
0
This parameter controls SMS sending
when IP address of GPRS connection is
changed. No warnings generated.
0:
no SMS on IP change
1:
SMS sent on IP change
E-mail on IP Change
-
0
1
0
This parameter controls e-mail sending
when IP address of GPRS or ethernet
connection is changed. No warnings
generated.
0:
no e-mail on IP change
1:
e-mail sent on IP change
Fuel Pump Low Limit
%
0
100
20
If the fuel level measured from the
sender input falls below this level, then
the FUEL PUMP function will become
active.
Fuel Pump High Limit
%
0
100
80
If the fuel level measured from the
sender input goes above this level, then
the FUEL PUMP function will become
passive.
Warning Before Start
-
0
1
1
This parameter controls the activation of
the ALARM output
during “Engine Start
Delay” timer before engine run.
0:
no warning before start
1:
warning before start
Latch all Warnings
-
0
1
0
0:
warnings are latching/non-latching on
parameter control
1:
all warnings are latched. Even if the
fault source is removed, warnings will
persist until manually reset.
Remote Control Enable
-
0
1
1
This parameter controls remote control
of the unit through Rainbow, Modbus
and Modbus TCP/IP.
0:
remote control disabled
1:
remote control enabled
Annunciator Mode
-
0
1
0
0:
normal operation
1:
the unit becomes an annunciator of
the remote unit. Engine/genset control
functions are disabled.
CT Location
-
Gen
Load
Gen
0:
CTs are at the genset side. Mains
currents are not measured.
1:
CTs are at load side. Both mains and
genset currents are monitored following
contactor status.
Reverse CT Direction
-
0
1
0
This parameter is useful to invert all CT
polarities at the same time.
0:
normal CT polarity assumed.
1:
reverse CT polarity assumed.
16.1. CONTROLLER CONFIGURATION GROUP (continued)
Summary of Contents for D-500
Page 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Page 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Page 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Page 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...