D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 148 -
ADDRESS
(decimal)
R / W
DATA
SIZE
COEFF.
DESCRIPTION
10504-
10519
R
256bit
-
Shutdown alarm bits. Bit definitions are given at the end of the
document.
10520-
10535
R
256bit
-
Loaddump alarm bits. Bit definitions are given at the end of the
document.
10536-
10551
R
256bit
-
Warning alarm bits. Bit definitions are given at the end of the
document.
10604
R
16bit
-
Unit operation status
0= genset at rest
1= wait before fuel
2= engine preheat
3= wait oil flash off
4=crank rest
5=cranking
6= engine run idle speed
7= engine heating
8= running off load
9= synchronizing to mains
10= load transfer to genset
11= gen cb activation
12= genset cb timer
13= master genset on load,
14= peak lopping
15= power exporting
16= slave genset on load
17= synchronizing back to mains
18= load transfer to mains
19= mains cb activation
20= mains cb timer
21= stop with cooldown
22= cooling down
23= engine stop idle speed
24= immediate stop
25= engine stopping
10605
R
16bit
-
Unit mode
0= STOP mode
1= AUTO mode
2= MANUAL mode
3= TEST mode
10606
R
16bit
x1
Genset operation timer. In various wait statuses, the genset
operation status will change at the expiration of this timer.
10610
R
16bit
-
Device hardware version information
10611
R
16bit
-
Device software version information
10616
R
32bit
x1
Counter: number of genset runs
10618
R
32bit
x1
Counter: number of genset cranks
10620
R
32bit
x1
Counter: number of genset on load
10622
R
32bit
x100
Counter: engine hours run
10624
R
32bit
x100
Counter: engine hours since last service
10626
R
32bit
x100
Counter: engine days since last service
10628
R
32bit
x10
Counter: genset total active energy (kWh)
10630
R
32bit
x10
Counter: genset total inductive reactive energy (kVArh-ind)
10632
R
32bit
x10
Counter: genset total capacitive reactive energy (kVArh-cap)
10634
R
32bit
x100
Counter: remaining engine hours to service-1
10636
R
32bit
x100
Counter: remaining engine days to service-1
10638
R
32bit
x100
Counter: remaining engine hours to service-2
10640
R
32bit
x100
Counter: remaining engine days to service-2
10642
R
32bit
x100
Counter: remaining engine hours to service-3
10644
R
32bit
x100
Counter: remaining engine days to service-3
Summary of Contents for D-500
Page 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Page 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Page 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Page 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...