D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 146 -
Modbus Slave Address:
may be set between 1 and 240
RS-485 Enable:
must be set to 1 (or checkbox enabled)
RS-485 Baud Rate:
selectable between 2400 and 115200 bauds. All devices in the same network must
use the same Baud Rate.
The complete RS-485 port specifications are found in the
D-500/700 User Manual
.
Selecting a higher baud rate will allow faster communication, but will reduce the communication distance.
Selecting a lower baud rate will increase the communication distance, but will cause slower response
times.
Typically 9600 bauds will allow 1200m distance with special balanced 120 ohms cable.
Modbus Slave Address:
may be set between 1 and 240. If only one unit is available in the same IP
address, it is advised to keep the default address (1).
Ethernet Enable:
This parameter should be set to 1 (or checked) in order to enable the ethernet port.
Modbus TCP/IP Port:
The usual setting is 502. However the unit is able to work on any port address.
User IP Mask:
There are 3 mask registers available. The use of the registers are emphasized in the D-
500/700 User Manual. Please set the first mask as 255.255.255.0 for the proper operation.
Ethernet Network IP:
May be left as 0.0.0.0 for automatic address claim or set to a value in order to
claim a defined address.
Ethernet Gateway IP:
Should be set in accordance with your local switch configuration.
Ethernet Subnet Mask:
Should be set in accordance with your local switch configuration.
The complete Ethernet port specifications are found in the
D-500/700 User Manual
.
Please rewiev the document
Ethernet Configuration Guide for D-500/700
for more details about the
ethernet port setup.
16bit variables:
These variables are stored in a single register. Bit_0 denotes the LSB and bit 15
denotes the MSB.
32 bit variables:
These variables are stored in 2 consecutive registers. The high order 16 bits are in the
first register and the low order 16 bits are in the second register
Bit arrays:
Arrays larger than 16 bits are stored in multiple registers. The LSB of the first register is bit_0.
The MSB of the first register is bit_15. The LSB of the second register is bit_16. The MSB of the second
register is bit_31, and so on.
33.3. DATA FORMATS
33.2. PARAMETERS REQUIRED FOR MODBUS-TCP/IP VIA ETHERNET
33.1. PARAMETERS REQUIRED FOR RS-485 MODBUS OPERATION
Summary of Contents for D-500
Page 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Page 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Page 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Page 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...