D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 127 -
The unit offers 2 ways of transferring the load from genset to mains and vice versa:
-transfer with interruption,
-no break transfer, (with or without synchronization)
This is the most conventional way of transferring the load between the genset and mains. There will be a
power interruption period during the transfer. Note that the program parameters
Mains Contactor Timer
and
Genset Contactor Timer
define the power interruption period.
Transfer from genset to mains:
-The generator contactor releases,
-The unit waits for Mains Contactor Timer
-The mains contactor is energized.
Transfer from mains to genset:
-The mains contactor releases,
-The unit waits for Generator Contactor Timer
-The generator contactor is energized.
If this transfer method is used, it is advised to make an electrical
interlock between the two contactors to prevent an accidental
phase to phase short circuit.
30.1. TRANSFER WITH INTERRUPTION
30. LOAD TRANSFER MODES
Summary of Contents for D-500
Page 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Page 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Page 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Page 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...