D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 83 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Buzzer Enable
-
0
1
1
Internal buzzer control (not functional in
D-500)
0:
buzzer disabled
1:
buzzer enabled
Unit Functionality
-
0
3
AMF
0:
AMF functionality. The unit controls
both engine and load transfer. The
genset starts based on mains status.
1:
ATS functionality. The unit controls
the load transfer and issues genset start
signal based on mains status.
2:
REMOTE START functionality. The
unit controls engine and alternator. The
genset starts with external signal.
3:
RESERVED. Not used.
Data Logging Period
sec
2
3600
2
This parameter adjusts the data logging
frequency to micro-SD or USB Flash
memories. Frequent recording will
require more memory capacity.
With a period of 2 seconds, 4GB per
year of memory is necessary.
With a period of 1 minute, 133MB is
consumed per year.
LCD Backlight Dimming
Delay
min
0
1440
60
If no button is pressed during this
period, then the unit will reduce the LCD
screen backlight intensity in for
economy.
Fuel Filling Timer
sec
0
36000
0
After activation of the fuel pump
function, if the
Fuel Pump High Limit
level is not reached, then the fuel pump
will stop for safety.
If this parameter is set to zero, then the
timer is unlimited.
SMS Commands
Enabled
-
0
1
0
0:
SMS commands not accepted
1:
SMS commands are accepted but
from listed telephone numbers only.
Open with Last Mode
-
0
1
0
0:
The unit powers up in STOP mode
1:
The unit powers up in the same
operating mode before power down.
Pre-Transfer Delay
sec
0
60
0
If this parameter is not zero, the unit will
activate the
Wait Before Transfer
output function during this timer, before
initiating a load transfer.
This function is designed for elevator
systems, in order to bring the cabin to a
floor and open doors before transfer.
E-mail on mains change
-
0
1
0
0:
No e-mail at mains status changes
1:
E-mails sent at mains status change
Enable Auto not Ready
Warning
-
0
1
0
0:
Auto not Ready Warning disabled
1:
Auto not Ready Warning enabled
Fuel Pulses from MPU
input
-
0
1
0
0: MPU input is used for engine
speed detection
1: MPU input is used for reading the
flowmeter pulses during fuel filling.
16.1. CONTROLLER CONFIGURATION GROUP (continued)
Summary of Contents for D-500
Page 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Page 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Page 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Page 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...