D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 79 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
LCD Contrast
-
30
50
31
This parameter is used to set LCD
contrast. Adjust for the best viewing
angle.
Screen Scroll Timer
sec
0
250
0
The screen will scroll between different
measurements with this interval. If set
to zero, the screen scroll will be
disabled.
Language
-
0
1
0
0:
English language selected.
1:
Local language selected. This
language may depend on the country
where the unit is intended to be used.
Genset Default Display
-
0
4
0
This parameter selects the screen
which is displayed during genset on
load operation.
0:
genset voltages table
1:
genset currents and freq. table
2:
genset kW and pf table
3:
genset kVA and kVAr table
4:
genset average measurements
Status Prompt Window
Enable
-
0
1
0
0:
Status prompts disabled
1:
Status prompts enabled
Fault Holdoff Timer
sec
0
120
12
This parameter defines the delay after
the engine runs and before the fault
monitoring is enabled.
Alarm Relay Timer
sec
0
120
60
This is the period during which the
ALARM
relay is active. If the period is
set to 0, this will mean that the period is
unlimited.
Intermittent Alarm Relay
-
0
1
0
0:
continuous
1:
intermittent (turns on and off every
second)
Emergency Backup
Operation
-
0
1
0
0:
In RUN mode, the load will not be
transferred to the genset even if the
mains fails.
1:
In RUN mode, the load will be
transferred to the genset if the mains
fails.
Exerciser Enable
-
0
1
0
0:
automatic exerciser disabled
1:
automatic exerciser enabled
Exercise Period
-
0
1
0
0:
exercise once per week
1:
exercise once per month
The exact exerciser day and time is
adjusted within the EXERCISE
SCHEDULE section.
Exercise Off/On Load
-
0
1
1
0:
Exercise at
RUN
mode
1:
Exercise at
TEST
mode
16. PROGRAM PARAMETER LIST
16.1. CONTROLLER CONFIGURATION GROUP
Summary of Contents for D-500
Page 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Page 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Page 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Page 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...