D-500 User Manual Rev_06 Firmware V-5.8
K35D05-EN - 48 -
Term Function
Technical data
Description
1
BATTERY POSITIVE
+12 or 24VDC
The positive terminal of the DC Supply.
2
-
-
Do not connect this terminal.
3
BATTERY NEGATIVE
O VDC
Power supply negative connection.
Term Function
Technical data
Description
4
DIGITAL OUTPUT 1
Protected
Semiconductor
Outputs
1A/28VDC
This relay has programmable function,
selectable from a list. Factory set as
CRANK
output.
5
DIGITAL OUTPUT 2
This relay has programmable function,
selectable from a list. Factory set as
FUEL
output.
6
DIGITAL OUTPUT 3
This relay has programmable function,
selectable from a list. Factory set as
ALARM
output.
7
DIGITAL OUTPUT 4
This relay has programmable function,
selectable from a list. Factory set as
PREHEAT
output.
8
DIGITAL OUTPUT 5
This relay has programmable function,
selectable from a list. Factory set as
STOP
output.
9
DIGITAL OUTPUT 6
This relay has programmable function,
selectable from a list. Factory set as
IDLE
SPEED
output.
10
CHARGE
Input and output
Connect the charge alternator’s D+
terminal to this terminal. This terminal will
supply the excitation current and measure
the voltage of the charge alternator.
11
DIGITAL INPUT 1
Digital Inputs,
0-30Vdc
The input has programmable function.
Factory set as
LOW OIL PRESSURE
SWITCH
.
12
DIGITAL INPUT 2
The input has programmable function.
Factory set as
HIGH TEMP SWITCH
.
7. TERMINAL DESCRIPTION
Summary of Contents for D-500
Page 44: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 44 6 3 ATS FUNCTIONALITY ...
Page 45: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 45 6 4 REMOTE START FUNCTIONALITY ...
Page 46: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 46 6 5 ENGINE CONTROL FUNCTIONALITY ...
Page 47: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 47 6 6 REMOTE DISPLAY PANEL FUNCTIONALITY ...
Page 56: ...D 500 User Manual Rev_06 Firmware V 5 8 K35D05 EN 56 ...