Handbuch Datafox EVO 3.5 Pure
Seite 82
Datum: 06.08.2018 Version: 04.03.07.XX
Several Internal Doors via RS485 Bus
The combined door-module is used here. The door opening relay is included in the com-
bined module. Caution: This assembly must not be used at outdoor locations because then the relay
is not within a protected area.
Installation plan:
Wire plan:
Button, for door open-
ing from inside
RS232 connection max. 15 m
Relay for door
Door monitoring
RS232/485
TCP/IP usw.
RS485 connection
max. 1000 m
Relay for door
Door monitoring
Door
– contact
Door monitoring
12V
+
-
Reader and door modul (LTM)
Art-Nr.:106030
ext. max. 30V 2A
Door opener
Reader and door modul (LTM)
Art-Nr.:106030
Door
– contact
Door monitoring
ext. max. 30V 2A
Door opener
Button, for door opening
from inside