VLT is a registered Danfoss trademark
Intro-9
Ratings Table 525-600V / 525-690V
Mains supply 3 x 525-690 V: 5000 & 8000 Series
Mains supply 3 x 525-600 V: 4000 & 6000 Series
Model number
VLT 4152 VLT 4202 VLT 4252 VLT 4302 VLT 4352 VLT 4402
VLT 5122 VLT 5152 VLT 5202 VLT 5252 VLT 5302 VLT 5352
VLT 6152 VLT 6172 VLT 6222 VLT 6272 VLT 6352 VLT 6402
VLT 8152 VLT 8202 VLT 8252 VLT 8302 VLT 8352 VLT 8402
Normal overload current ratings (110 %):
Output current
Nominal [A] (525-550 V)
162
204
253
303
360
418
MAX (60 sec) [A] (525-550 V)
178
224
278
333
396
460
Nominal [A] (551-690 V)
155
192
242
290
344
400
MAX (60 sec) [A] (551-690 V)
171
211
266
319
378
440
Output
Nominal [kVA] (550 V)
154
194
241
289
343
398
Nominal [kVA] (575 V)
154
191
241
289
343
398
Nominal [kVA] (690 V)
185
229
289
347
411
478
Typical shaft output
[kW] (550 V)
110
132
160
200
250
315
[HP] (575 V)
150
200
250
300
350
400
[kW] (690 V)
132
160
200
250
315
400
High overload torque (160 %):
Output current
Nominal [A] (525-550 V)
137
162
204
253
303
360
MAX (60 sec) [A] (525-550 V)
206
243
306
380
455
540
Nominal [A] (551-690 V)
131
155
192
242
290
344
MAX (60 sec) [A] (551-690 V)
197
233
288
363
435
516
Output
Nominal [kVA] (550 V)
131
154
194
241
289
343
Nominal [kVA] (575 V)
130
154
191
241
289
343
Nominal [kVA] (690 V)
157
185
229
289
347
411
Typical shaft output
[kW] (550 V)
90
110
132
160
200
250
[HP] (575 V)
125
150
200
250
300
350
[kW] (690 V)
110
132
160
200
250
315
Power loss Normal overload [W]
3114
3612
4293
5155
5821
6149
Power loss High overload [W]
2665
2953
3451
4275
4875
5185
Limits and Ranges
Warning Voltage Low
DC Bus V
585
585
585
585
585
585
Alarm Voltage Low
DC Bus V
553
553
553
553
553
553
Warning Voltage High
DC Bus V
1109
1109
1109
1109
1109
1109
Alarm Voltage High
DC Bus V
1120
1120
1120
1120
1120
1120
Brake On Voltage
DC Bus V
1084
1084
1084
1084
1084
1084
Brake On Voltage (Full Duty Cycle)
DC Bus V
1099
1099
1099
1099
1099
1099
SMPS Start Voltage
DC Bus V
508
508
508
508
508
508
SMPS Stop Voltage
DC Bus V
478
478
478
478
478
478
Overcurrent Warning
VLT Out
361
466
683
683
827
1038
Overcurrent Alarm (1.5 sec delay)
VLT Out
361
466
683
683
827
1038
Earth Fault Alarm
VLT Out
66
78
96
121
145
172
Heatsink Over Temperature
Degrees C
75
80
100
100
100
100
Mains Phase Warning (5 sec delay)
DC Bus Ripple VAC
70
70
70
70
70
70
Mains Phase Alarm (25 sec delay)
DC Bus Ripple VAC
70
70
70
70
70
70
Fan On Low Speed Temperature
Degrees C
45
45
45
45
45
45
Fan On High Sped Temperature
Degrees C
50
50
50
50
50
50
Fan Off Temperature
Degrees C
<30
<30
<30
<30
<30
<30
Fan Voltage Low Speed
Fan VAC
200
200
200
200
200
200
Fan Voltage High Speed
Fan VAC
230
230
230
230
230
230