3-13
VLT is a registered Danfoss trademark
3.4 AFTER REPAIR TESTS
Following any repair to a drive or testing of a drive suspected
of being faulty, the following procedure must be followed to
ensure that all circuitry in the drive is functioning properly before
putting the unit into operation.
1. Perform visual inspection procedures as
described in Table 3-1.
2. Perform static test procedures 5.1.1., 5.1.2 and
5.1.5 for D-frame size units or 5.1.3, 5.1.4 and
5.1.5 for E-frame size units to ensure drive is
safe to start.
3. Disconnect motor leads from output terminals
(U, V, W) of drive.
4. Apply AC power to drive.
5. Give drive a run command and slowly increase
reference (speed command) to approximately 40
Hz.
6. Using an analog volt meter or a DVM capable of
measuring true RMS, measure phase-to-phase
output voltage on all three phases: U to V, U to
W, V to W. All voltages must be balanced within
8 volts. If unbalanced voltage is measured, refer
to Input Voltage Test (5.2.1.1).
7. Stop drive and remove input power.
Allow 40
minutes for DC capacitors to fully discharge
for E-frame size drives or 20 minutes for D-
frame size drives.
8. Reconnect motor leads to drive output terminals
(U, V, W).
9. Reapply power and restart drive. Adjust motor
speed to a nominal level.
10. Using a clamp-on style ammeter, measure
output current on each output phase. All
currents should be balanced. If unbalanced
current is measured, refer to Current Sensor
Test (5.2.12).
Summary of Contents for VLT series
Page 1: ...MOTION CONTROLS Service Manual VLT 4152 4652 VLT 5122 5602 VLT 6152 6652 VLT 8152 8652...
Page 8: ......
Page 20: ......
Page 32: ......
Page 41: ...2 9 VLT is a registered Danfoss trademark Figure 2 7 Inverter Section...
Page 58: ......
Page 96: ......
Page 152: ......