Ratings Table 380-500V
Mains supply 3 x 380-500 V
Model number
VLT 4452 VLT 4502 VLT 4602 VLT 4652
VLT 5352 VLT 5452 VLT 5502 VLT 5552
VLT 6402 VLT 6502 VLT 6552 VLT 6602
VLT 8452 VLT 8502 VLT 8602 VLT 8652
Normal overload current ratings (110 %):
Output current
Nominal [A] (380-440 V)
600
658
745
800
MAX (60 sec) [A] (380-440 V)
660
724
820
880
Nominal [A] (441-500 V)
540
590
678
730
MAX (60 sec) [A] (441-500 V)
594
649
746
803
Output
Nominal [kVA] (400 V)
416
456
516
554
Nominal [kVA] (460 V)
430
470
540
582
Nominal [kVA] (500 V)
468
511
587
632
Typical shaft output
[kW] (400 V)
315
355
400
450
[HP] (460 V)
450
500
550/600
600
[kW] (500 V)
355
400
500
530
High overload torque (160 %):
Output current
Nominal [A] (380-440 V)
480
600
658
695
MAX (60 sec) [A] (380-440 V)
720
900
987
1043
Nominal [A] (441-500 V)
443
540
590
678
MAX (60 sec) [A] (441-500 V)
665
810
885
1017
Output
Nominal [kVA] (400 V)
333
416
456
482
Nominal [kVA] (460 V)
353
430
470
540
Nominal [kVA] (500 V)
384
468
511
587
Typical shaft output
[kW] (400 V)
250
315
355
400
[HP] (460 V)
350
450
500
550
[kW] (500 V)
315
355
400
500
Power loss Normal overload [W]
7630
7701
8879
9428
Power loss High overload [W]
6005
6960
7691
7964
Limits and Ranges
Warning Voltage Low
DC Bus V
423
423
423
423
Alarm Voltage Low
DC Bus V
402
402
402
402
Warning Voltage High
DC Bus V
817
817
817
817
Alarm Voltage High
DC Bus V
855
855
855
855
Brake On Voltage
DC Bus V
795
795
795
795
Brake On Voltage (Full Duty Cycle)
DC Bus V
810
810
810
810
SMPS Start Voltage
DC Bus V
360
360
360
360
SMPS Stop Voltage
DC Bus V
330
330
330
330
Overcurrent Warning
VLT Out
888
1202
1202
1202
Overcurrent Alarm (1.5 sec delay)
VLT Out
888
1202
1202
1202
Earth Fault Alarm
VLT Out
265
322
352
405
Heatsink Over Temperature
Degrees C
85
85
85
85
Mains Phase Warning (5 sec delay)
DC Bus Ripple VAC
70
70
70
70
Mains Phase Alarm (25 sec delay)
DC Bus Ripple VAC
70
70
70
70
Fan On Low Speed Temperature
Degrees C
45
45
45
45
Fan On High Sped Temperature
Degrees C
50
50
50
50
Fan Off Temperature
Degrees C
<30
<30
<30
<30
Fan Voltage Low Speed
Fan VAC
200
200
200
200
Fan Voltage High Speed
Fan VAC
230
230
230
230
Summary of Contents for VLT series
Page 1: ...MOTION CONTROLS Service Manual VLT 4152 4652 VLT 5122 5602 VLT 6152 6652 VLT 8152 8652...
Page 8: ......
Page 20: ......
Page 32: ......
Page 41: ...2 9 VLT is a registered Danfoss trademark Figure 2 7 Inverter Section...
Page 58: ......
Page 96: ......
Page 152: ......