6.
Remove soft charge resistor by removing two
mounting screws.
Reassembly
1.
Clean heatsink surface with mild solvent or alcohol
solution.
2.
Reassemble remaining parts in reverse order of
their removal. Tighten T25 and 8mm mounting
screws to 20 in-lbs (2.25 Nm) and T30 and 10
mm to 35 in-lbs (4 Nm).
Soft Charge Resistor
Figure 6-8. D1 Soft Charge Resistor (3 of 3)