10 Troubleshooting
10.1 LED Status
130BD780.10
MS LED
NS LED’s
MCA 120
PROFINET
SW. ver. 3.00 (TM: 3:15)
MS
NS2
NS1
Ethernet Port 1
Ethernet Port 2
MAC: 00:1B:08:XX:XX:XX
Option A
130B1135
Host Name
8 7 6 5 4 3 2 1
Illustration 10.1 LED
Status
Tri-colour LED
No IP Address assigned
Off
No Communication to PROFINET module. Module is waiting for
configuration telegram from Controller.
Green:
IO AR established
Green:
Supervisor AR established, No IO AR.
Green:
▂███▂███▂█
Internal Error
Red:
▂█▂█▂█▂█▂█
Wink
Yellow:
▂█▂█▂█▂█▂█
Table 10.1 MS: Module Status
Network Status
Phases
Status
Tri-colour LED
Power Off
No Power or No Link on the corresponding port
Off
Power On
IP Address Conflict
Red:
Waiting for configuration
Green:
▂█▂█▂█▂█▂█
Running
In Data Exchange Mode
Green:
Wrong Configuration
Red:
▂███▂███▂█
Data exchange
No increment in "In Octets" counter of
corresponding port in last 60 s
Yellow:
▂█▂█▂█▂█▂█
Table 10.2 Indication on Network Status LED
Troubleshooting
Operating Instructions
MG90U302
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
63
10
10