If
[0] Digital input
is selected, the terminals control the
Coast and DC Brake functions.
NOTICE
Coasting, Quick Stop, and DC brake functions are active
for logic 0.
Terminal
Bit 02/03/04
Function
0
0
Coast/DC brake/Q-Stop
0
1
Coast/DC brake/Q-Stop
1
0
No Coast/DC brake/Q-Stop
1
1
No Coast/DC brake/Q-Stop
Table 10.4 [0] Digital Input
If
[1] Serial communication
is selected, commands are
activated only when given via serial communication.
Terminal
Bit 02/03/04
Function
0
0
Coast/DC brake/Q-Stop
0
1
No Coast/DC brake/Q-Stop
1
0
Coast/DC brake/Q-Stop
1
1
No Coast/DC brake/Q-Stop
Table 10.5 [1] Serial Communication
If
[2] Logic AND
is selected, both signals must be activated
to perform the function.
Terminal
Bit 02/03/04
Function
0
0
Coast/DC brake/Q-Stop
0
1
No Coast/DC brake/Q-Stop
1
0
No Coast/DC brake/Q-Stop
1
1
No Coast/DC brake/Q-Stop
Table 10.6 [2] Logic AND
If
[3] Logic OR
is selected, activation of one signal activates
the function.
Terminal
Bit 02/03/04
Function
0
0
Coast/DC brake/Q-Stop
0
1
Coast/DC brake/Q-Stop
1
0
Coast/DC brake/Q-Stop
1
1
No Coast/DC brake/Q-Stop
Table 10.7 [3] Logic OR
The effect of control mode upon the function of
8-53 Start
Select
and
parameter 8-54 Reversing Select
:
If
[0] Digital input
is selected, the terminals control the start
and reversing functions
Terminal
Bit 06/15
Function
0
0
Stop/Anti-clockwise
0
1
Stop/Anti-clockwise
1
0
Start/Clockwise
1
1
Start/Clockwise
Table 10.8 [0] Digital input
If
[1] Serial communication
is selected, commands are
activated only when given via serial communication.
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Start/Clockwise
1
0
Stop/Anti-clockwise
1
1
Start/Clockwise
Table 10.9 [1] Serial Communication
If
[2] Logic AND
is selected, both signals must be activated
to perform the function.
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Stop/Anti-clockwise
1
0
Stop/Anti-clockwise
1
1
Start/Clockwise
Table 10.10 [2] Logic AND
If
[3] Logic OR
is selected, activation of one signal activates
the function.
Terminal
Bit 02/03/04
Function
0
0
Stop/Anti-clockwise
0
1
Start/Clockwise
1
0
Start/Clockwise
1
1
Start/Clockwise
Table 10.11 [3] Logic OR
The effect of control mode upon the function of
8-55 Set-
up Select
and
8-56 Preset Reference Select
:
If
[0] Digital input
is selected, the terminals control the set-
up and preset reference functions.
Troubleshooting
Operating Instructions
MG90U302
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
65
10
10