By using the hardware switches it is possible to set 253
different station names according to
Table 3.3
(FC 302 used
in this example):
Switch
8
7
6
5
4
3
2
1
12-08 Host Name
+128 +64 +32 +16 +8
+4
+2
+1
‘FC-302-005’
OFF OFF OFF OFF OFF ON OFF ON
‘FC-302-035’
OFF OFF ON OFF OFF OFF ON ON
‘FC-302-082’
OFF
ON OFF ON OFF OFF ON OFF
‘FC-302-212’
ON
ON OFF ON OFF ON OFF OFF
Table 3.3 Host Names Setting
The Host Name change comes into effect at the next
power-up, and can be read in
12-08 Host Name
.
3.3 LED Behaviour
The option has 3 bi-coloured LEDs that allow a fast and
detailed diagnosis. The 3 LEDs are each linked to its
unique part of the PROFINET option, see
Table 3.4
.
LED label
Description
MS
Module Status, reflects the activity on the
PROFINET stack
NS1
Network Status 1, reflects the activity on port 1
NS2
Network Status 2, reflects the activity on port 2
Table 3.4 LED Label
130BD784.10
MS LED
NS LED’s
MCA 120
PROFINET
SW. ver. 3.00 (TM: 3:15)
MS
NS2
NS1
Ethernet Port 1
Ethernet Port 2
MAC: 00:1B:08:XX:XX:XX
Option A
130B1135
Host Name
8 7 6 5 4 3 2 1
Ethernet Port 1
Ethernet Port 2
Illustration 3.13 Overview of the Option
130BD804.10
ON
WARNING
ALARM
Bus MS
NS1
NS2
Illustration 3.14 LED Panel for FCD 302
The LED is visible from the outside of an FCD 302.
How to Install
Operating Instructions
16
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
MG90U302
3
3