Module status
Status
Tri-colour LED
No IP Address assigned
Off
No Communication to PROFINET module. Module is waiting for configu-
ration telegram from Controller.
Green:
IO AR established
Green:
Supervisor AR established, No IO AR.
Green:
▂███▂███▂█
Internal Error
Red:
▂█▂█▂█▂█▂█
Wink
Yellow:
▂█▂█▂█▂█▂█
Table 3.5 MS: Module Status
Network Status
Phases
Status
Tri-colour LED
Power Off
No Power or No Link on the corresponding port
Off
Power On
IP Address Conflict
Red:
Waiting for configuration
Green:
▂█▂█▂█▂█▂█
Running
In Data Exchange Mode
Green:
Wrong Configuration
Red:
▂███▂███▂█
Data exchange
No increment in "In Octets" counter of
corresponding port in last 60 s
Yellow:
▂█▂█▂█▂█▂█
Table 3.6 Indication on Network Status LED
During normal operation the MS and at least one NS LED shows a constant green light.
Wink command
The option responds to a Wink command from the network by yellow flashing of all 3 LEDs simultaneously.