Illustration 9.1
Program the frequency converter as shown in
Table 9.2
:
Parameter
Setting
4-10 Motor Speed Direction
[2] Both directions
5-10 Terminal 18 Digital Input
[0] No operation
5-11 Terminal 19 Digital Input
[10] Reversing
5-40 Function Relay
[36/37] Control word bit 11/12
Parameter 8-03 Control Timeout Time
1 s
Parameter 8-04 Control Timeout Function
[2] Stop
Parameter 8-10 Control Profile
[0] FC Profile
8-50 Coasting Select
[1] Bus
Parameter 8-51 Quick Stop Select
[1] Bus
8-52 DC Brake Select
[1] Bus
8-53 Start Select
[1] Bus
Parameter 8-54 Reversing Select
[2] Logic AND
8-55 Set-up Select
[1] Bus
8-56 Preset Reference Select
[1] Bus
9-16 PCD Read Configuration
[2] Sub index
16-16 Torque [Nm]
[3] Sub indes
16-60 Digital Input
Table 9.2
Application Examples
Operating Instructions
MG90U302
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
59
9
9