Power range
N500
N560
Drive modules
2
2
Rectifier configuration
12-pulse
High/normal load
HO
NO
HO
NO
Output current [A]
Continuous (at 550 V)
523
596
596
630
Intermittent (60 s overload) at 550 V
785
656
894
693
Continuous (at 575/690 V)
500
570
570
630
Intermittent (60 s overload) at 575/690 V
750
627
627
693
Input current [A]
Continuous (at 550 V)
504
574
574
607
Continuous (at 575 V)
482
549
549
607
Continuous (at 690 V)
482
549
549
607
Power losses [W]
Drive modules at 600 V
6016
6995
6941
7431
Drive modules at 690 V
5886
6831
6766
7638
AC bus bars at 575 V
546
550
550
553
DC bus bars during regeneration
186
186
191
191
Maximum cable size [mm
2
(mcm)]
Mains
4x120 (250)
Motor
4x120 (250)
Brake
4x95 (3/0)
Regeneration terminals
1)
4x120 (250)
Maximum external mains fuses
700 V, 630 A
Table 7.13 FC 302, 525–690 V AC Mains Supply (2-Drive System)
1) If Danfoss bus bar kit is used.
Specifications
Installation Guide
MG37K302