![Danfoss VLT HVAC Drive FC 102 Installation Manual Download Page 57](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-fc-102/vlt-hvac-drive-fc-102_installation-manual_3411614057.webp)
Power range
N500
N560
N630
N710
N800
Drive modules
4
4
4
4
4
Rectifier configuration
6-pulse/12-pulse
High/normal load
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Output current [A]
Continuous (at 380–440 V)
880
990
990
1120
1120
1260
1260
1460
1460
1720
Intermittent (60 s overload) at 400 V
1320
1089
1485
1232
1680
1386
1890
1606
2190
1892
Continuous (at 460/500 V)
780
890
890
1050
1050
1160
1160
1380
1380
1530
Intermittent (60 s overload) at 460/500 V
1170
979
1335
1155
1575
1276
1740
1518
2070
1683
Input current [A]
Continuous (at 400 V)
857
964
964
1090
1090
1227
1227
1422
1422
1675
Continuous (at 460/500 V)
759
867
867
1022
1022
1129
1129
1344
1344
1490
Power losses [W]
Drive modules at 400 V
7713
8810
8918
10199
10181
11632
11390
13253
13479
16463
Drive modules at 460 V
6641
7628
7855
9324
9316
10375
12391
12391
12376
13958
AC bus bars at 400 V
655
665
665
680
680
695
695
722
722
762
AC bus bars at 460 V
647
656
656
671
671
683
683
710
710
732
DC bus bars during regeneration
218
218
232
232
250
276
276
276
318
318
Maximum cable size [mm
2
(mcm)]
Mains
4x185 (350)
8x120 (250)
Motor
4x185 (350)
8x120 (250)
Brake
8x70 (2/0)
8x95 (3/0)
Regeneration terminals
1)
6x125 (250)
8x125 (250)
8x150 (300)
10x150 (300)
Maximum external mains fuses
6-pulse configuration
600 V, 1600 A
600 V, 2000 A
600 V, 2500 A
12-pulse configuration
600 V, 900 A
600 V, 1500 A
Table 7.11 FC 302, 380–500 V AC Mains Supply (4-Drive System)
1) If Danfoss bus bar kit is used.
Specifications
Installation Guide
MG37K302
Danfoss A/S © 08/2017 All rights reserved.
55
7
7