![Danfoss VLT HVAC Drive FC 102 Installation Manual Download Page 55](http://html1.mh-extra.com/html/danfoss/vlt-hvac-drive-fc-102/vlt-hvac-drive-fc-102_installation-manual_3411614055.webp)
Power range
N710
N800
N900
N1M0
N1M2
Drive modules
4
4
4
4
4
Rectifier configuration
6-pulse/12-pulse
High/normal load
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Output current [A]
Continuous (at 550 V)
659
763
763
889
889
988
988
1108
1108
1317
Intermittent (60 s overload) at 550 V
989
839
1145
978
1334
1087
1482
1219
1662
1449
Continuous (at 575/690 V)
630
730
730
850
850
945
945
1060
1060
1260
Intermittent (60 s overload) at
575/690 V
945
803
1095
935
1275
1040
1418
1166
1590
1590
Input current [A]
Continuous (at 550 V)
642
743
743
866
866
962
1079
1079
1079
1282
Continuous (at 575 V)
613
711
711
828
828
920
1032
1032
1032
1227
Continuous (at 690 V)
613
711
711
828
828
920
1032
1032
1032
1227
Power losses [W]
Drive modules at 575 V
7469
8683
8668
10166
10163
11406
11292
12852
12835
15762
Drive modules at 690 V
7381
8559
8555
9996
9987
11188
11077
12580
12551
15358
AC bus bars at 575 V
637
644
644
653
653
661
661
672
672
695
DC bus bars during regeneration
198
198
208
208
218
218
231
231
256
256
Maximum cable size [mm
2
(mcm)]
Mains
4x120 (250)
6x120 (250)
8x120 (250)
Motor
4x120 (250)
6x120 (250)
8x120 (250)
Brake
8x70 (2/0)
8x95 (3/0)
Regeneration terminals
1)
4x150 (300)
6x120 (250)
6x150 (300)
8x120 (250)
Maximum external mains fuses
6-pulse configuration
700 V, 1600 A
700 V, 2000 A
12-pulse configuration
700 V, 900 A
700 V, 1500 A
Table 7.9 FC 202, 525–690 V AC Mains Supply (4-Drive System)
1) If Danfoss bus bar kit is used.
Specifications
Installation Guide
MG37K302
Danfoss A/S © 08/2017 All rights reserved.
53
7
7