Power range
N500
N560
N630
Drive modules
2
2
2
Rectifier configuration
12-pulse
High/normal load
HO
NO
HO
NO
HO
NO
Output current [A]
Continuous (at 550 V)
429
523
523
596
596
630
Intermittent (60 s overload) at 550 V
644
575
785
656
894
693
Continuous (at 575/690 V)
410
500
500
570
570
630
Intermittent (60 s overload) at 575/690 V
615
550
750
627
627
693
Input current [A]
Continuous (at 550 V)
413
504
504
574
574
607
Continuous (at 575 V)
395
482
482
549
549
607
Continuous (at 690 V)
395
482
482
549
549
607
Power losses [W]
Drive modules at 575 V
4892
6076
6016
6995
6941
7431
Drive modules at 690 V
4797
5951
5886
6831
6766
7638
AC bus bars at 575 V
542
546
546
550
550
553
DC bus bars during regeneration
91
91
186
186
191
191
Maximum cable size [mm
2
(mcm)]
Mains
4x120 (250)
Motor
4x120 (250)
Brake
4x70 (2/0)
4x95 (3/0)
Regeneration terminals
1)
4x120 (250)
Maximum external mains fuses
700 V, 630 A
Table 7.8 FC 202, 525–690 V AC Mains Supply (2-Drive System)
1) If Danfoss bus bar kit is used.
Specifications
VLT
®
Parallel Drive Modules
52
Danfoss A/S © 08/2017 All rights reserved.
MG37K302
7
7