Power range
N315
N400
N450
Drive modules
2
2
2
Rectifier configuration
12-pulse
High/normal load
HO
NO
HO
NO
HO
NO
Output current [A]
Continuous (at 550 V)
303
360
360
418
395
470
Intermittent (60 s overload) at 550 V
455
396
560
460
593
517
Continuous (at 575/690 V)
290
344
344
400
380
450
Intermittent (60 s overload) at 575/690 V
435
378
516
440
570
495
Input current [A]
Continuous (at 550 V)
299
355
355
408
381
453
Continuous (at 575 V)
286
339
339
490
366
434
Continuous (at 690 V)
296
352
352
400
366
434
Power losses [W]
Drive modules at 575 V
3688
4401
4081
4789
4502
5457
Drive modules at 690 V
3669
4352
4020
4709
4447
5354
AC bus bars at 575 V
538
540
540
541
540
544
DC bus bars during regeneration
88
88
89
89
90
90
Maximum cable size [mm
2
(mcm)]
Mains
2x120 (250)
4x120 (250)
Motor
2x120 (250)
4x120 (250)
Brake
4x70 (2/0)
Regeneration terminals
1)
4x120 (250)
Maximum external mains fuses
700 V, 550 A
Table 7.7 FC 202, 525–690 V AC Mains Supply (2-Drive System)
1) If Danfoss bus bar kit is used.
Specifications
Installation Guide
MG37K302
Danfoss A/S © 08/2017 All rights reserved.
51
7
7