Power range
N560
N630
N710
N800
N1M0
Drive modules
4
4
4
4
4
Rectifier configuration
6-pulse/12-pulse
High/normal load
NO
NO
NO
NO
NO
Output current [A]
Continuous (at 380–440 V)
990
1120
1260
1460
1720
Intermittent (60 s overload) at 400 V
1089
1232
1386
1606
1892
Continuous (at 460/500 V)
890
1050
1160
1380
1530
Intermittent (60 s overload) at 460/500 V
979
1155
1276
1518
1683
Input current [A]
Continuous (at 400 V)
964
1090
1227
1422
1675
Continuous (at 460/500 V)
867
1022
1129
1344
1490
Power losses [W]
Drive modules at 400 V
8810
10199
11632
13253
16463
Drive modules at 460 V
7628
9324
10375
12391
13958
AC bus bars at 400 V
665
680
695
722
762
AC bus bars at 460 V
656
671
683
710
732
DC bus bars during regeneration
218
232
250
276
318
Maximum cable size [mm
2
(mcm)]
Mains
4x185 (350)
8x120 (250)
Motor
4x185 (350)
8x120 (250)
Brake
8x70 (2/0)
8x95 (3/0)
Regeneration terminals
1)
6x120 (250)
8x120 (250)
8x150 (300) 10x150 (300)
Maximum external mains fuses
6-pulse configuration
600 V,
1600 A
600 V, 2000 A
600 V, 2500 A
12-pulse configuration
600 V, 700 A
600 V, 900 A
600 V,
1500 A
Table 7.2 FC 102, 380–480 V AC Mains Supply (4-Drive System)
1) If Danfoss bus bar kit is used.
Specifications
VLT
®
Parallel Drive Modules
46
Danfoss A/S © 08/2017 All rights reserved.
MG37K302
7
7