Reinforced protective ground
Mains supply
L1
L2
L3
PE
PLC
Control cables
Minimum 16 mm
2
equalizing cable
Minimum 200 mm
between control
cables, motor cable,
and mains cable
Motor, 3-phases and protective ground
PLC, etc.
Panel
Output contactor, etc.
Ground rail
Cable insulation stripped
All cable entries in 1 side of panel
130BA048.14
Illustration 5.13 EMC-correct Electrical Installation of a Frequency Converter in Cabinet
Electrical Installation
VLT
®
Parallel Drive Modules
38
Danfoss A/S © 08/2017 All rights reserved.
MG37K302
5
5