7.1.2 VLT
®
AQUA Drive FC 202
Power range
N315
N355
N400
N450
N500
Drive modules
2
2
2
2
2
Rectifier configuration
12-pulse
6-pulse/12-pulse
High/normal load
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Output current [A]
Continuous (at 400 V)
480
588
600
658
658
745
695
800
810
880
Intermittent (60 s overload) at 400 V
720
647
900
724
987
820
1043
880
1215
968
Continuous (at 460/500 V)
443
535
540
590
590
678
678
730
730
780
Intermittent (60 s overload) at
460/500 V
665
588
810
649
885
746
1017
803
1095
858
Input current [A]
Continuous (at 400 V)
463
567
590
647
647
733
684
787
779
857
Continuous (at 460/500 V)
427
516
531
580
580
667
667
718
711
759
Power losses [W]
Drive modules at 400 V
4505
5825
5502
6110
6110
7069
6375
7538
7526
8468
Drive modules at 460 V
4063
4998
5384
5964
5271
6175
6070
6609
6604
7140
AC bus bars at 400 V
545
550
551
555
555
561
557
565
566
575
AC bus bars at 460 V
543
548
548
551
551
556
556
560
560
563
DC bus bars during regeneration
93
93
95
95
98
98
101
101
105
105
Maximum cable size [mm
2
(mcm)]
Mains
4x120 (250)
4x150 (300)
Motor
4x120 (250)
4x150 (300)
Brake
4x70 (2/0)
4x95 (3/0)
Regeneration terminals
1)
4x120 (250)
6x120 (250)
6x120 (250)
Maximum external mains fuses
6-pulse configuration
–
–
–
–
600 V, 1600 A
12-pulse configuration
600 V, 700 A
600 V, 900 A
Table 7.5 FC 202, 380–480 V AC Mains Supply (2-Drive System)
1) If Danfoss bus bar kit is used.
Specifications
Installation Guide
MG37K302
Danfoss A/S © 08/2017 All rights reserved.
49