Power range
N315
N400
N450
N500
N560
N630
Drive modules
2
2
2
2
2
2
Rectifier configuration
12-pulse
High/normal load
NO
NO
NO
NO
NO
NO
Output current [A]
Continuous (at 550 V)
360
418
470
523
596
630
Intermittent (60 s overload) at 550 V
396
360
517
575
656
693
Continuous (at 575/690 V)
344
400
450
500
570
630
Intermittent (60 s overload) at 575/690 V
378
440
495
550
627
693
Input current [A]
Continuous (at 550 V)
355
408
453
504
574
607
Continuous (at 575 V)
339
490
434
482
549
607
Continuous (at 690 V)
352
400
434
482
549
607
Power losses [W]
Drive modules at 575 V
4401
4789
5457
6076
6995
7431
Drive modules at 690 V
4352
4709
5354
5951
6831
7638
AC bus bars at 575 V
540
541
544
546
550
553
DC bus bars during regeneration
88
88.5
90
91
186
191
Maximum cable size [mm
2
(mcm)]
Mains
2x120 (250)
4x120 (250)
Motor
2x120 (250)
4x120 (250)
Brake
4x70 (2/0)
4x95 (3/0)
Regeneration terminals
1)
4x120 (250)
Maximum external mains fuses
700 V, 550 A
700 V, 630 A
Table 7.3 FC 102, 525–690 V AC Mains Supply (2-Drive System)
1) If Danfoss bus bar kit is used.
Specifications
Installation Guide
MG37K302
Danfoss A/S © 08/2017 All rights reserved.
47
7
7