14-63 Min Switch Frequency
Set the minimum switching frequency allowed by the output
filter.
Option:
Function:
[2]
*
2.0 kHz
[3]
3.0 kHz
[4]
4.0 kHz
[5]
5.0 kHz
[6]
6.0 kHz
[7]
8.0 kHz
[8]
10.0 kHz
[9]
12.0 kHz
[10]
16.0 kHz
14-64 Dead Time Compensation Zero Current Level
For a long motor cable, set this parameter to
[0] Disabled
to
minimize the motor-torque ripple.
Option:
Function:
[0]
*
Disabled
[1]
Enabled
14-65 Speed Derate Dead Time Compensation
Range:
Function:
Size
related
*
[ 20 -
1000 Hz]
Deadtime compensation level is reduced
linearly in relation to output frequency.
Parameter 14-07 Dead Time Compensation
Level
sets the maximum level. The
minimum output frequency level is
defined in
4.11.8 14-8* Options
14-89 Option Detection
Selects the behavior when an option change is detected. This
parameter returns to
[0] Protect Option Config.
after an option
change.
Option:
Function:
[0]
*
Protect Option Config. Freezes the current settings and
prevents unwanted changes when
missing or defective options are
detected.
[1]
Enable Option
Change
Settings can be changed when the
system configuration is being
modified.
4.11.9 14-9* Fault Settings
Fault customization settings
14-90 Fault Level
Use this parameter to customize fault levels. Setting the
parameter value may change
parameter 1–73 Flying Start
.
Option:
Function:
[3]
*
Trip lock
[4]
Trip with delayed reset
[5]
Flystart
Parameters
VLT
®
DriveMotor FCP 106/FCM 106
92
Danfoss A/S © 11/2015 All rights reserved.
MG03N202
4
4