4.13 Main Menu - Data Readouts - Group 16
4.13.1 16-0* General Status
16-00 Control Word
Range:
Function:
0
*
[0 - 65535 ] View the control word sent from the frequency
converter via the serial communication port in
hex code.
Bit Bit=0
Bit=1
00 Preset reference option lsb
–
01 Preset reference option 2
nd
bit of
preset references
–
02 DC brake
Ramp
03 Coasting
Enable
04 Quick stop
Ramp
05 Freeze output
Ramp
06 Ramp stop
Start
07 No function
Reset
08 No function
Jog
09 Ramp 1
Ramp 2
10 Data not valid
Valid
11 Relay_A not active
Relay_A activated
12 Relay_B not active
Relay_B activated
13 Choice of set-up lsb
–
14 No function
No function
15 No function
Reversing
Table 4.8 Control Word
16-01 Reference [Unit]
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-4999 - 4999
ReferenceFeed-
backUnit]
View the present reference
value applied on impulse
or analog basis in the unit
resulting from the configu-
ration selected in
parameter 1-00 Configu-
ration Mode
(Hz).
16-02 Reference [%]
Range:
Function:
0 %
*
[-200 - 200 %] View the total reference. The total
reference is the sum of digital, analog,
preset, bus, and freeze references.
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ] View the status word sent from the frequency
converter via the serial communication port in
hex code.
Bit Bit=0
Bit=1
00 Control not ready
Ready
01 VLT not ready
Ready
02 Coasting
Enable
03 No fault
Trip
04 No warning
Warning
05 Reserved
–
06 No trip lock
Trip lock
07 No warning
Warning
08 Speed
≠
ref.
Speed=ref.
09 Local control
Bus control
10 Out of range
Frequency OK
11 Not running
Running
12 No function
No function
13 Voltage OK
Above limit
14 Current OK
Above limit
15 Temperature OK
Above limit
Table 4.9 Status Word
16-05 Main Actual Value [%]
Range:
Function:
0 %
*
[-200 - 200 %] View the 2-byte word sent with the status
word to the bus master reporting the
main actual value.
16-09 Custom Readout
Range:
Function:
0 CustomRea-
doutUnit
*
[0 - 9999
CustomRea-
doutUnit]
View the user-defined readouts
as defined in
parameter 0-30 Custom Readout
Unit
, and
parameter 0-32 Custom Readout
Max Value
4.13.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
*
[0 - 1000
kW]
Shows DC link power in kW. The value
shown is calculated based on the actual
motor voltage and motor current.
16-11 Power [hp]
Range:
Function:
0 hp
*
[0 - 1000
hp]
View the the actual motor power in hp. The
value shown is calculated on the basis of
the actual motor voltage and motor
current.
Parameters
VLT
®
DriveMotor FCP 106/FCM 106
96
Danfoss A/S © 11/2015 All rights reserved.
MG03N202