Alarm/
warning
number
Fault text
Warning
Alarm
Trip lock Cause of problem
2
Live zero error
X
X
–
Signal on terminal 53 or 54 is less than 50% of value set in:
•
Parameter 6-10 Terminal 53 Low Voltage
•
Parameter 6-12 Terminal 53 Low Current
•
Parameter 6-20 Terminal 54 Low Voltage
•
Parameter 6-22 Terminal 54 Low Current
See also parameter group
6–0* Analog In/Out
.
3
No motor
X
–
–
A motor has not been connected to the frequency converter.
4
Mains ph. loss
X
X
X
Missing phase on supply side or excess voltage imbalance. Check
supply voltage. See
parameter 14-12 Function at Mains Imbalance
7
DC over volt
X
X
–
DC-link voltage exceeds limit.
8
DC under volt
X
X
–
DC-link voltage is lower than voltage warning low-limit.
9
Inverter
overload
X
X
–
More than 100% load for too long.
10
Motor ETR over
X
X
–
Motor is overheated due to more than 100% load for too long. See
parameter 1-90 Motor Thermal Protection
.
11
Motor th over
X
X
–
Thermistor or thermistor connection is disconnected. See
parameter 1-90 Motor Thermal Protection
.
13
Over Current
X
X
X
Inverter peak current limit is exceeded.
14
Earth Fault
X
X
X
Discharge from output phases to ground.
16
Short Circuit
–
X
X
Short circuit in motor or on motor terminals.
17
Control word
timeout
X
X
–
No communication to frequency converter. See parameter group
8-0*
Comm. and Options.
24
Fan fault
–
–
–
External fans have failed either due to defect hardware, or due to
missing fans.
30
U phase loss
–
X
X
Motor phase U is missing. Check the phase. See
.
31
V phase loss
–
X
X
Motor phase V is missing. Check the phase. See
.
32
W phase loss
–
X
X
Motor phase W is missing. Check the phase. See
.
34
Fieldbus fault
X
–
–
–
35
Option fault
–
X
–
–
36
Mains failure
X
–
–
–
38
Internal fault
–
X
X
Contact the local Danfoss supplier.
40
Overload T27
X
–
–
–
41
Overload T29
X
–
–
–
46
Gate drive
voltage fault
–
X
X
–
47
Control voltage
fault
X
X
X
24 V DC is possibly overloaded.
51
AMA U
nom
, I
nom
–
X
–
The setting of motor voltage, motor current, and motor power is
presumably wrong. Check the settings.
52
AMA low I
nom
–
X
–
The motor current is too low. Check the settings.
53
AMA motor too
big
–
X
–
The motor is too large to perform AMA.
54
AMA motor too
small
–
X
–
The motor is too small to perform AMA.
55
AMA parameter
out of range
–
X
–
The parameter values found from the motor are outside acceptable
range.
Diagnostics and Troubleshoo...
VLT
®
DriveMotor FCP 106/FCM 106
118
Danfoss A/S © 11/2015 All rights reserved.
MG03N202
5
5