0-20 Display Line 1.1 Small
Option:
Function:
[1601] Reference [Unit]
Total reference (sum of digital/analog/
preset/bus/freeze ref./catch up and
slow down) in selected unit.
[1602]
*
Reference [%]
Total reference (sum of digital/analog/
preset/bus/freeze ref./catch up and
slow down) in percent.
[1603] Status Word
Present status word.
[1605] Main Actual
Value [%]
View the 2-byte word sent with the
status word to the bus master
reporting the main actual value.
[1609] Custom Readout
View the user-defined readouts as
defined in
parameter 0-30 Custom
Readout Unit
,
parameter 0-31 Custom
Readout Min Value
, and
parameter 0-32 Custom Readout Max
Value
.
[1610] Power [kW]
Actual power consumed by the motor
in kW.
[1611] Power [hp]
Actual power consumed by the motor
in hp.
[1612] Motor Voltage
Voltage supplied to the motor.
[1613] Frequency
Motor frequency, that is, the output
frequency from the frequency
converter in Hz.
[1614] Motor current
Phase current of the motor measured
as effective value.
[1615] Frequency [%]
Motor frequency, that is, the output
frequency from the frequency
converter in percent.
[1616] Torque [Nm]
Present motor load as a percentage
of the rated motor torque.
[1618] Motor Thermal
Thermal load on the motor,
calculated by the ETR function. See
also parameter group 1-9* Motor
Temperature.
[1622] Torque [%]
Shows the actual torque produced, in
percentage.
[1626] Power Filtered
[kW]
[1627] Power Filtered
[hp]
[1630] DC Link Voltage
DC-link voltage in the frequency
converter.
[1634] Heatsink Temp.
Present heat sink temperature of the
frequency converter. The cut-out limit
is 95 ± 5
°
C; cutting back in occurs at
70
±
5
°
C.
[1635] Inverter Thermal
Percentage load of the inverters.
0-20 Display Line 1.1 Small
Option:
Function:
[1636] Inv. Nom. Current Nominal current of the frequency
converter.
[1637] Inv. Max. Current
Maximum current of the frequency
converter.
[1638] SL Controller
State
State of the event executed by the
control.
[1639] Control Card
Temp.
Temperature of the control card.
[1650] External
Reference
Sum of the external reference as a
percentage, that is, the sum of
analog/pulse/bus.
[1652] Feedback[Unit]
Reference value from programmed
digital inputs.
[1660] Digital Input
Shows the status of the digital inputs.
Signal low = 0; Signal high = 1.
Regarding order, see
parameter 16-60 Digital Input
. Bit 0 is
at the extreme right.
[1661] Terminal 53
Setting
Setting of input terminal 53. Current
= 0; Voltage = 1.
[1662] Analog Input
AI53
Actual value at input 53 either as a
reference or protection value.
[1663] Terminal 54
Setting
Setting of input terminal 54. Current
= 0; Voltage = 1.
[1664] Analog Input
AI54
Actual value at input 54 either as
reference or protection value.
[1665] Analog Output
AO42 [mA]
Actual value at output 42 in mA. Use
parameter 6-50 Terminal 42 Output
to
select the variable to be represented
by output 42.
[1666] Digital Output
Binary value of all digital outputs.
[1667] Pulse Input #29
[Hz]
Actual value of the frequency applied
at terminal 29 as a pulse input.
[1671] Relay Output
[bin]
View the setting of all relays.
[1672] Counter A
View the present value of Counter A.
[1673] Counter B
View the present value of Counter B.
[1679] Analog Output
AO45
[1680] Fieldbus CTW 1
Control word (CTW) received from
the Bus Master.
[1682] Fieldbus REF 1
Main reference value sent with
control word via the serial communi-
cations network for example, from
the BMS, PLC, or other master
controller.
[1684] Comm. Option
STW
Extended fieldbus communication
option status word.
Parameters
VLT
®
DriveMotor FCP 106/FCM 106
36