3-15 Reference 1 Source
Option:
Function:
The sum of these reference signals defines
the actual reference.
[0]
No function
[1]
*
Analog Input
53
[2]
Analog Input
54
[7]
Pulse input 29
[11] Local bus
reference
3-16 Reference 2 Source
Option:
Function:
Select the input to be used for the 2nd
reference signal.
parameter 3-16 Reference 2 Source
,
and
parameter 3-17 Reference 3 Source
define up to 3 different reference signals.
The sum of these reference signals defines
the actual reference. See also
parameter 1-93 Thermistor Source
.
[0]
No function
[1]
Analog Input
53
[2]
*
Analog Input
54
[7]
Pulse input 29
[11] Local bus
reference
3-17 Reference 3 Source
Option:
Function:
Select the reference input to be used for
the 3rd reference signal.
Parameter 3-15 Reference 1 Source
,
parameter 3-16 Reference 2 Source
, and
parameter 3-17 Reference 3 Source
define
up to 3 different reference signals. The
sum of these reference signals defines the
actual reference.
[0]
No function
[1]
Analog Input
53
[2]
Analog Input
54
[7]
Pulse input 29
[11]
*
Local bus
reference
4.4.3 3-4* Ramp 1
Configure the ramp time parameters, for each of the 2
ramps (parameter group
3-4* Ramp 1
and parameter group
3-5* Ramp 2
). The ramp time is preset to the minimum
value of 10 ms for all power sizes.
t
acc
t
dec
130BB801.10
P 3-*2
Ramp (X)
Down
Time (Dec)
P 4-14
High-limit
RPM
Reference
P 1-23
Motor
frequency
P 4-12
Low limit
Time
P 3-*1
Ramp (X)Up
Time (Acc)
Illustration 4.8 Ramps
3-41 Ramp 1 Ramp Up Time
Range:
Function:
Size
related
*
[0.05 -
3600 s]
Enter acceleration time from 0 Hz to
parameter 1-23 Motor Frequency
if
asynchronous motor is selected. Enter
acceleration time from 0 RPM, to
parameter 1-25 Motor Nominal Speed
if PM
motor is selected. Select a ramp-up time
such that the output current does not
exceed the current limit in
parameter 4-18 Current Limit
during ramping.
See ramp-down time in
parameter 3-42 Ramp 1 Ramp Down Time
.
3-42 Ramp 1 Ramp Down Time
Range:
Function:
Size
related
*
[0.05 -
3600 s]
If asynchronous motor is selected, enter
deceleration time from
parameter 1-23 Motor Frequency
to 0 Hz. If
PM motor is selected, enter deceleration
time from
to 0 RPM. Select a ramp-down time
to avoid tripping on overvoltage in the
DC-link.
Parameters
Programming Guide
MG03N202
Danfoss A/S © 11/2015 All rights reserved.
53
4
4