5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Default values for
parameter 5–40 Function Relay
:
When
parameter 0-03 Regional Settings
is set to
[0] International
,
the default value of Relay1 is Alarm, and default value of Relay2
is Drive Running.
When
parameter 0-03 Regional Settings
is set to
[1] North America
,
the default value of Relay1 is No Alarm, and default value of
Relay2 is Drive Running.
Option:
Function:
[36]
Control word
bit 11
Bit 11 in control word controls relay.
[37]
Control word
bit 12
Bit 12 in control word controls relay.
[41]
Below
reference, low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
See parameter group
13-1* Comparators
.
If comparator 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61]
Comparator 1
See parameter group
13-1* Comparators
.
If comparator 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62]
Comparator 2
See parameter group
13-1* Comparators
.
If comparator 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63]
Comparator 3
See parameter group
13-1* Comparators
.
If comparator 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64]
Comparator 4
See parameter group
13-1* Comparators
.
If comparator 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65]
Comparator 5
See parameter group
13-1* Comparators
.
If comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70]
Logic rule 0
See parameter group
13-4* Logic Rules
. If
logic rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71]
Logic rule 1
See parameter group
13-4* Logic Rules
. If
logic rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72]
Logic rule 2
See parameter group
13-4* Logic Rules
. If
logic rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73]
Logic rule 3
See parameter group
13-4* Logic Rules
. If
logic rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Default values for
parameter 5–40 Function Relay
:
When
parameter 0-03 Regional Settings
is set to
[0] International
,
the default value of Relay1 is Alarm, and default value of Relay2
is Drive Running.
When
parameter 0-03 Regional Settings
is set to
[1] North America
,
the default value of Relay1 is No Alarm, and default value of
Relay2 is Drive Running.
Option:
Function:
[74]
Logic rule 4
See parameter group
13-4* Logic Rules
. If
logic rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75]
Logic rule 5
See parameter group
13-4* Logic Rules
. If
logic rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80]
SL digital
output A
See
parameter 13-52 SL Controller Action
The input goes high whenever the smart
logic action
[38] Set dig. out. A high
is
executed. The input goes low whenever
the smart logic
[32] Action Set dig. out. A
low
is executed.
[81]
SL digital
output B
See
parameter 13-52 SL Controller Action
The input goes high whenever the smart
logic action
[39] Set dig. out. B high
is
executed. The input goes low whenever
the smart logic
[33] Action Set dig. out. B
low
is executed.
[82]
SL digital
output C
See
parameter 13-52 SL Controller Action
The input goes high whenever the smart
logic action
[40] Set dig. out. C high
is
executed. The input goes low whenever
the smart logic
[34] Action Set dig. out. C
low
is executed.
[83]
SL digital
output D
See
parameter 13-52 SL Controller Action
The input goes high whenever the smart
logic
[41] Action Set dig. out. D
high is
executed. The input goes low whenever
the smart logic
[35] Action Set dig. out. D
low
is executed.
[160] No alarm
The output is high when no alarm is
present.
[161] Running
reverse
The output is high when the frequency
converter runs counterclockwise (the
logical product of the status bits running
AND reverse).
[165] Local ref. active The output is high when
parameter 3-13 Reference Site
=
[2] Local
or when
parameter 3-13 Reference Site
=
Parameters
Programming Guide
MG03N202
Danfoss A/S © 11/2015 All rights reserved.