5-34 On Delay, Digital Output
Range:
Function:
0.01 s
*
[0 - 600 s] Enter the delay time before the digital
output is switched on. The digital output
(terminal 42/45) condition must not be
interrupted during the delay time.
5-35 Off Delay, Digital Output
Range:
Function:
0.01 s
*
[0 - 600 s] Enter the delay time before the digital
output is switched off. The digital output
(terminal 42/45) condition must not be
interrupted during the delay time.
4.6.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Default values for
parameter 5–40 Function Relay
:
When
parameter 0-03 Regional Settings
is set to
[0] International
,
the default value of Relay1 is Alarm, and default value of Relay2
is Drive Running.
When
parameter 0-03 Regional Settings
is set to
[1] North America
,
the default value of Relay1 is No Alarm, and default value of
Relay2 is Drive Running.
Option:
Function:
[0]
No operation
Default for both relays.
[1]
Control Ready
The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for
operation and applies supply signal on
control board.
[3]
Drive ready/
remote control
The frequency converter is ready for
operation in Auto On mode.
[4]
Standby / no
warning
The frequency converter is ready for
operation. No start or stop command is
given. No warnings are present.
[5]
Drive running
The motor runs.
[6]
Running / no
warning
The motor runs, and no warnings are
present.
[7]
Run in
range/no
warning
The motor runs within programmed
current ranges, see
parameter 4-50 Warning Current Low
and
parameter 4-51 Warning Current High
. No
warnings are present.
[8]
Run on ref/no
warning
The motor runs at reference speed and
with no warnings.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realized in an array
parameter.
Default values for
parameter 5–40 Function Relay
:
When
parameter 0-03 Regional Settings
is set to
[0] International
,
the default value of Relay1 is Alarm, and default value of Relay2
is Drive Running.
When
parameter 0-03 Regional Settings
is set to
[1] North America
,
the default value of Relay1 is No Alarm, and default value of
Relay2 is Drive Running.
Option:
Function:
[9]
Alarm
An alarm activates output.
[10]
Alarm or
warning
An alarm or warning activates output.
[12]
Out of current
range
The motor current is outside the range
set in
parameter 4-50 Warning Current Low
and
parameter 4-51 Warning Current High
[13]
Below current,
low
The motor current is lower than set in
parameter 4-50 Warning Current Low
.
[14]
Above current,
high
The motor current is higher than set in
parameter 4-51 Warning Current High
[16]
Below speed,
low
[17]
Above speed,
high
[19]
Below
feedback, low
[20]
Above
feedback, high
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in motor,
frequency converter, or thermistor.
[22]
Ready, no
thermal
warning
The frequency converter is ready for
operation and no overtemperature
warning is present.
[23]
Remote, ready,
no thermal
warning
The frequency converter is ready for
operation in Auto mode, and no overtem-
perature warning is present.
[24]
Ready, Voltage
OK
The frequency converter is ready for
operation, and mains voltage is within
specified voltage range.
[25]
Reverse
The motor runs/is ready to run clockwise
when logic = 0 and counterclockwise
when logic = 1. Output changes when
reversing signal is applied.
[26]
Bus OK
Active communication (no timeout) via
serial communication port.
[32]
Mech brake ctrl
[35]
External
Interlock
See digital input.
Parameters
VLT
®
DriveMotor FCP 106/FCM 106
62