Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conversion
index
Type
20-84 On Reference Bandwidth
5%
All set-ups
TRUE
0
Uint8
20-9* PI Controller
20-91 PI Anti Windup
[1] On
All set-ups
TRUE
-
Uint8
20-93 PI Proportional Gain
0.50 N/A
All set-ups
TRUE
-2
Uint16
20-94 PI Integral Time
20 s
All set-ups
TRUE
-2
Uint32
20-97 PI Feed Forward Factor
0%
All set-ups
TRUE
0
Uint16
6.1.17 22-** Appl. Functions
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conversion
index
Type
22-0* Miscellaneous
22-01 Power Filter Time
0.50 s
2 set-ups
TRUE
-2
Uint16
22-02 Sleepmode CL Control Mode
[0] Normal
All set-ups
TRUE
-
Uint8
22-2* No-Flow Detection
22-26 Dry Pump Function
[0] Off
All set-ups
TRUE
-
Uint8
22-27 Dry Pump Delay
10 s
All set-ups
TRUE
0
Uint16
22-3* No-Flow Power Tuning
22-38 High Speed Power [kW]
ExpressionLimit
All set-ups
TRUE
1
Uint32
22-4* Sleep Mode
22-40 Minimum Run Time
10 s
All set-ups
TRUE
0
Uint16
22-41 Minimum Sleep Time
10 s
All set-ups
TRUE
0
Uint16
22-43 Wake-Up Speed [Hz]
10 N/A
All set-ups
TRUE
-1
Uint16
22-44 Wake-Up Ref./FB Diff
10%
All set-ups
TRUE
0
Uint8
22-45 Setpoint Boost
0%
All set-ups
TRUE
0
Int8
22-46 Maximum Boost Time
60 s
All set-ups
TRUE
0
Uint16
22-47 Sleep Speed [Hz]
0 N/A
All set-ups
TRUE
-1
Uint16
22-48 Sleep Delay Time
0 s
All set-ups
TRUE
0
Uint16
22-49 Wake-Up Delay Time
0 s
All set-ups
TRUE
0
Uint16
22-5* End of Curve
22-50 End of Curve Function
[0] Off
All set-ups
TRUE
-
Uint8
22-51 End of Curve Delay
10 s
All set-ups
TRUE
0
Uint16
22-6* Broken Belt Detection
22-60 Broken Belt Function
[0] Off
All set-ups
TRUE
-
Uint8
22-61 Broken Belt Torque
10%
All set-ups
TRUE
0
Uint8
22-62 Broken Belt Delay
10 s
All set-ups
TRUE
0
Uint16
22-8* Flow Compensation
22-80 Flow Compensation
[0] Disabled
All set-ups
TRUE
-
Uint8
22-81 Square-linear Curve Approximation
100%
All set-ups
TRUE
0
Uint8
22-82 Work Point Calculation
[0] Disabled
All set-ups
TRUE
-
Uint8
22-84 Speed at No-Flow [Hz]
0 Hz
All set-ups
TRUE
-1
Uint16
22-86 Speed at Design Point [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
22-87 Pressure at No-Flow Speed
0 N/A
All set-ups
TRUE
-3
Uint32
22-88 Pressure at Rated Speed
999999.999 N/A
All set-ups
TRUE
-3
Uint32
22-89 Flow at Design Point
0 N/A
All set-ups
TRUE
-3
Int32
22-90 Flow at Rated Speed
0 N/A
All set-ups
TRUE
-3
Int32
Parameter Lists
Programming Guide
MG03N202
Danfoss A/S © 11/2015 All rights reserved.
139