525–690 V
Enclosure
Power [kW]
Recommended fuse size
Recommended
max. fuse
Recommended circuit
breaker
Danfoss
Max. trip level
[A]
A3
1.5 [1.1]
gG-6
gG-25
CTI25M 10-16
16
2 [1.5]
gG-6
gG-25
CTI25M 10-16
16
3 [2.2]
gG-6
gG-25
CTI25M 10-16
16
4 [3]
gG-10
gG-25
CTI25M 10-16
16
5 [4]
gG-10
gG-25
CTI25M 10-16
16
7.5 [5.5]
gG-16
gG-25
CTI25M 10-16
16
10 [7.5]
gG-16
gG-25
CTI25M 10-16
16
B2
15 [11]
gG-25
gG-63
15
gG-25
gG-63
24 [18]
gG-32
30 [22]
gG-32
C2
40 [30]
gG-40
50 [37]
gG-63
gG-80
60 [45]
gG-63
gG-100
75 [55]
gG-80
gG-125
100 [75]
gG-100
gG-160
C3
50 [37]
gG-100
gG-125
60 [45]
gG-125
gG-160
Table 8.16 525–690 V, Enclosure Types A, B, C
Specifications
VLT
®
AQUA Drive FC 202
70
Danfoss A/S © 10/2014 All rights reserved.
MG20MA22
8
8