525–600 V
Enclosure
Power [kW]
Recommended
fuse size
Recommended
max. fuse
Recommended circuit
breaker
Moeller
Max. trip level [A]
A2
1.5–5 [1.1–4.0]
gG-10
gG-25
PKZM0-25
25
A3
7.5–10 [5.5–7.5]
gG-10 (7.5 [5.5])
gG-16 (10 [7.5])
gG-32
PKZM0-25
25
A5
1.5–10 [1.1–7.5]
gG-10 (1–7.5 [0.75–5.5])
gG-16 (10 [7.5])
gG-32
PKZM0-25
25
B1
15–25 [11–18]
gG-25 (15 [11])
gG-32 (20 [15])
gG-40 (25 [18.5])
gG-80
PKZM4-63
63
B2
30–40 [22–30]
gG-50 (30 [22])
gG-63 (40 [30])
gG-100
NZMB1-A100
100
B3
15–25 [11–18.5]
gG-25 (15 [11])
gG-32 (20 [15])
gG-63
PKZM4-50
50
B4
30–50 [22–37]
gG-40 (25 [18.5])
gG-50 (30 [22])
gG-63 (40 [30])
gG-125
NZMB1-A100
100
C1
50–75 [37–55]
gG-63 (50 [37])
gG-100 (60 [45])
aR-160 (75 [55])
gG-160 (50–60 [37–45])
aR-250 (75 [55])
NZMB2-A200
160
C2
100–125 [75–90]
aR-200 (100 [75])
aR-250
NZMB2-A250
250
C3
60–75 [45–55]
gG-63 (50 [37])
gG-100 (60 [45])
gG-150
NZMB2-A200
150
C4
100–125 [75–90]
aR-160 (75 [55])
aR-200 (100 [75])
aR-250
NZMB2-A250
250
Table 8.15 525–600 V, Enclosure Types A, B and C
Specifications
Instruction Manual
MG20MA22