Symptom
Possible cause
Test
Solution
Acoustic noise
or vibration
Resonances
Bypass critical frequencies by using
parameters in parameter group
4-6* Speed
Bypass
.
Check if noise and/or vibration have been
reduced to an acceptable limit.
Turn off over-modulation in
14-03 Overmo-
dulation
.
Change switching pattern and frequency in
parameter group
14-0* Inverter Switching
.
Increase Resonance Dampening in
1-64 Resonance Damping
.
Table 7.6 Troubleshooting
Maintenance, Diagnostics an...
Instruction Manual
MG20MA22
Danfoss A/S © 10/2014 All rights reserved.
51
7
7