3x525–600 V
Recommended max. fuse
Power
[kW]
Bussmann
Type RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
SIBA
Type RK1
Littelfuse
Type RK1
Ferraz-
Shawmut
Type RK1
Ferraz-
Shawmut
J
1–1.5
[0.75–1.1]
KTS-R-5
JKS-5
JJS-6
FNQ-R-5
KTK-R-5
LP-CC-5
5017906-
005
KLS-R-005
A6K-5-R
HSJ-6
2–3
[1.5–2.2]
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
5017906-
010
KLS-R-010 A6K-10-R
HSJ-10
4 [3]
KTS-R15
JKS-15
JJS-15
FNQ-R-15
KTK-R-15
LP-CC-15
5017906-
016
KLS-R-015 A6K-15-R
HSJ-15
5 [4]
KTS-R20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5017906-
020
KLS-R-020 A6K-20-R
HSJ-20
7.5 [5.5]
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
5017906-
025
KLS-R-025 A6K-25-R
HSJ-25
10 [7.5]
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
5017906-
030
KLS-R-030 A6K-30-R
HSJ-30
15–20
[11–15]
KTS-R-35
JKS-35
JJS-35
-
-
-
5014006-
040
KLS-R-035 A6K-35-R
HSJ-35
24 [18]
KTS-R-45
JKS-45
JJS-45
-
-
-
5014006-
050
KLS-R-045 A6K-45-R
HSJ-45
30 [22]
KTS-R-50
JKS-50
JJS-50
-
-
-
5014006-
050
KLS-R-050 A6K-50-R
HSJ-50
40 [30]
KTS-R-60
JKS-60
JJS-60
-
-
-
5014006-
063
KLS-R-060 A6K-60-R
HSJ-60
50 [37]
KTS-R-80
JKS-80
JJS-80
-
-
-
5014006-
080
KLS-R-075 A6K-80-R
HSJ-80
60 [45]
KTS-R-100
JKS-100
JJS-100
-
-
-
5014006-
100
KLS-R-100
A6K-
100-R
HSJ-100
75 [55]
KTS-R-125
JKS-125
JJS-125
-
-
-
2028220-
125
KLS-R-125
A6K-
125-R
HSJ-125
75
KTS-R-150
JKS-150
JJS-150
-
-
-
2028220-
150
KLS-R-150
A6K-
150-R
HSJ-150
125 [90]
KTS-R-175
JKS-175
JJS-175
-
-
-
2028220-
200
KLS-R-175
A6K-
175-R
HSJ-175
Table 8.23 3x525–600 V, Enclosure Types A, B and C
1) 170M fuses shown from Bussmann use the -/80 visual indicator. –TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and
amperage may be substituted.
Specifications
VLT
®
AQUA Drive FC 202
74
Danfoss A/S © 10/2014 All rights reserved.
MG20MA22
8
8