6.1.5 RS-485
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1
R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
-
61
68
69
RS-485
+
130BB685.10
Function
Setting
8-30 Protocol
FC*
8-31 Address
1*
8-32 Baud Rate
9600*
* = Default Value
Notes/comments:
Select protocol, address and
baud rate in the above-
mentioned parameters.
D IN 37 is an option.
Table 6.11 RS-485 Network Connection
6.1.6 Motor Thermistor
CAUTION
THERMISTOR INSULATION
Risk of equipment damage exists.
•
Use only thermistors with reinforced or double
insulation to meet PELV insulation
requirements.
Parameters
130BB686.12
VLT
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Function
Setting
1-90 Motor
Thermal
Protection
[2]
Thermistor
trip
1-93 Thermistor
Source
[1] Analog
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to [1]
Thermistor
warning
.
D IN 37 is an option.
Table 6.12 Motor Thermistor
Application Set-up Examples
VLT
®
AQUA Drive FC 202
36
Danfoss A/S © 10/2014 All rights reserved.
MG20MA22
6
6