8.1.5 Line Power Supply 3x525–600 V AC
Type Designation
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
P11K
Typical Shaft Output [kW]
0.75
1.1
1.5
2.2
3.0
4.0
5.5
7.5
11
IP20/Chassis
A2
A2
A2
A2
A2
A2
A3
A3
B3
IP21/Type 1
A2
A2
A2
A2
A2
A2
A3
A3
B1
IP55/Type 12
A5
A5
A5
A5
A5
A5
A5
A5
B1
IP66/NEMA 4X
A5
A5
A5
A5
A5
A5
A5
A5
B1
Output current
Continuous (3 x 525–550 V) [A]
1.8
2.6
2.9
4.1
5.2
6.4
9.5
11.5
19
Intermittent (3 x 525–550 V) [A]
-
2.9
3.2
4.5
5.7
7.0
10.5
12.7
21
Continuous (3x525–600 V) [A]
1.7
2.4
2.7
3.9
4.9
6.1
9.0
11.0
18
Intermittent (3x525–600 V) [A]
-
2.6
3.0
4.3
5.4
6.7
9.9
12.1
20
Continuous kVA (525 V AC) [kVA]
1.7
2.5
2.8
3.9
5.0
6.1
9.0
11.0
18.1
Continuous kVA (575 V AC) [kVA]
1.7
2.4
2.7
3.9
4.9
6.1
9.0
11.0
17.9
Max. input current
Continuous (3x525–600 V) [A]
1.7
2.4
2.7
4.1
5.2
5.8
8.6
10.4
17.2
Intermittent (3x525–600 V) [A]
-
2.7
3.0
4.5
5.7
6.4
9.5
11.5
19
Max. pre-fuses
1)
[A]
10
10
10
20
20
20
32
32
40
Additional specifications
Estimated power loss
at rated max. load [W]
4)
35
50
65
92
122
145
195
261
225
Max. cable size (line power, motor,
brake) [mm
2
]/(AWG)
2)
[0.2–4]/(24–10)
[16]/(6)
Efficiency
3)
0.97
0.97
0.97
0.97
0.97
0.97
0.97
0.97
0.98
Table 8.7 Line Power Supply 3x525–600 V AC - Normal overload 110% for 1 minute, PK75-P11K
Specifications
Instruction Manual
MG20MA22
Danfoss A/S © 10/2014 All rights reserved.
57
8
8