Type Designation
P11K
P15K
P18K
P22K
Typical Shaft output at 550 V [kW]
11
15
18.5
22
Typical Shaft output at 690 V [kW]
15
18.5
22
30
IP20/Chassis
B4
B4
B4
B4
IP21/Type 1, IP55/Type 12
B2
B2
B2
B2
Output current
Continuous (3 x 525–550 V) [A]
19.0
23.0
28.0
36.0
Intermittent (60 s overload) (3x525–550 V) [A]
20.9
25.3
30.8
39.6
Continuous (3x551–690 V) [A]
18.0
22.0
27.0
34.0
Intermittent (60 s overload) (3x551–690 V) [A]
19.8
24.2
29.7
37.4
continuous KVA (at 550 V) [KVA]
18.1
21.9
26.7
34.3
continuous KVA (at 690 V AC) [KVA]
21.5
26.3
32.3
40.6
Max. input current
Continuous (at 550 V) (A)
19.5
24.0
29.0
36.0
Intermittent (60 s overload) (at 550 V) (A)
21.5
26.4
31.9
39.6
Continuous (at 690 V) (A)
19.5
24.0
29.0
36.0
Intermittent (60 s overload) (at 690 V) (A)
21.5
26.4
31.9
39.6
Additional specifications
Max. cable cross-section
5)
for line power/motor,
load share and brake [mm
2
] ([AWG])
35, 25, 25 (2, 4, 4)
Max cable cross-section
54)
for line power
disconnect [mm
2
] ([AWG])
16,10,10 (6, 8, 8)
Estimated power loss at rated max. load (W)
4)
220
300
370
440
Efficiency
3)
0.98
0.98
0.98
0.98
Table 8.10 B2/B4 Enclosure, Line Power Supply 3x525–690 V AC IP20/IP21/IP55 - Chassis/NEMA 1/NEMA 12, P11K-P22K
Specifications
Instruction Manual
MG20MA22
Danfoss A/S © 10/2014 All rights reserved.
59
8