8.8.1 CE Compliance
200–240 V
Enclosure
Power [kW]
Recommended
fuse size
Recommended
max. fuse
Recommended circuit
breaker
Moeller
Max. trip level [A]
A2
0.34–3 [0.25–2.2]
gG-10 (0.34–2 [0.25–1.5])
gG-16 (3 [2.2])
gG-25
PKZM0-25
25
A3
4–5 [3.0–3.7]
gG-16 (4 [3])
gG-20 (5 [3.7])
gG-32
PKZM0-25
25
A4
0.34–3 [0.25–2.2]
gG-10 (0.34–2 [0.25–1.5])
gG-16 (3 [2.2])
gG-32
PKZM0-25
25
A5
0.34–5 [0.25–3.7]
gG-10 (0.34–2 [0.25–1.5])
gG-16 (3–4 [2.2–3])
gG-20 (5 [3.7])
gG-32
PKZM0-25
25
B1
7.5–15 [5.5–11]
gG-25 (7.5 [5.5])
gG-32 (10 [7.5])
gG-80
PKZM4-63
63
B2
15
gG-50
gG-100
NZMB1-A100
100
B3
7.5–15 [5.5–11]
gG-25
gG-63
PKZM4-50
50
B4
11–24 [15–18]
gG-32 (10 [7.5])
gG-50 (15 [11])
gG-63 (20 [15])
gG-125
NZMB1-A100
100
C1
25–40 [18.5–30]
gG-63 (20 [15])
gG-80 (25 [18.5])
gG-100 (30 [22])
gG-160 (20–25 [15-18.5])
aR-160 (30 [22])
NZMB2-A200
160
C2
50–60 [37–45]
aR-160 (40 [30])
aR-200 (50 [37])
aR-200 (40 [30])
aR-250 (50 [37])
NZMB2-A250
250
C3
30–40 [22–30]
gG-80 (25 [18.5])
aR-125 (30 [22])
gG-150 (25 [18.5])
aR-160 (30 [22])
NZMB2-A200
150
C4
50–60 [37–45]
aR-160 (40 [30])
aR-200 (50 [37])
aR-200 (40 [30])
aR-250 (50 [37])
NZMB2-A250
250
Table 8.13 200–240 V, Enclosure Types A, B and C
Specifications
Instruction Manual
MG20MA22
Danfoss A/S © 10/2014 All rights reserved.
67
8
8