Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
CAUTION
!
It is very important that values set in param-
eters 102,
Motor Power, through 106, Rated Motor
Speed, correspond accurately to nameplate data
of motor.
102
Motor Power
(MOTOR POWER)
Value:
0.25 kW
(0.33 HP)
[25]
0.37 kW
(0.5 HP)
[37]
0.55 kW
(0.75 HP)
[55]
0.75 kW
(1 HP)
[75]
1.1 kW
(1.5 HP)
[110]
1.5 kW
(2 HP)
[150]
2.2 kW
(3 HP)
[220]
3 kW
--
[300]
4 kW
(5 HP)
[400]
5.5 kW
(7.5 HP)
[550]
7.5 kW
(10 HP)
[750]
11 kW
(15 HP)
[1100]
15 kW
(20 HP)
[1500]
18.5 kW
(25 HP)
[1850]
22 kW
(30 HP)
[2200]
30 kW
(40 HP)
[3000]
37 kW
(50 HP)
[3700]
45 kW
(60 HP)
[4500]
55 kW
(75 HP)
[5500]
75 kW
(100 HP)
[7500]
90 kW
(125 HP)
[9000]
110 kW
(150 HP)
[11000]
132 kW
(175 HP)
[13200]
160 kW
(200 HP)
[16000]
200 kW
(300 HP)
[20000]
250 kW
--
[25000]
300 kW
--
[30000]
315 kW
(350 HP)
[31500]
355 kW
(450 HP)
[35500]
400 kW
(500 HP)
[40000]
500 kW
(600 HP)
[50000]
★
Depends on the unit
Function:
Set the power value that corresponds to the nameplate power of the
motor. The default setting is the full rating of the drive.
Description of choice:
Select a value that equals the nameplate data on the motor. It is also
possible to set any power within the range of the drive.
103
Motor Voltage
(MOTOR VOLTAGE)
Value:
200 V
[200]
208 V
[208]
220 V
[220]
230 V
[230]
240 V
[240]
380 V
[380]
400 V
[400]
415 V
[415]
440 V
[440]
460 V
[460]
480 V
[480]
500 V
[500]
575 V
[575]
★
Depends on the unit
Function:
Set the rated motor voltage.
Description of choice:
Select a value that equals the nameplate data on the motor. This may
be less than the input voltage. It is also possible to set any voltage
within the range of the drive.
104
Motor Frequency
(MOTOR FREQUENCY)
Value:
50 Hz (50 Hz)
[50]
★
60 Hz (60 Hz)
[60]
Function:
This is where the rated motor frequency is selected. This is usually the
frequency of the power line.
Description of choice:
Select the desired value. It is also possible to set any frequency within
the range of the drive.
CAUTION
!
Enter correct value in parameter 105,
Motor Cur-
rent, since this forms part of VVC
+
control.
Changing values in parameter 102,
Motor Power,
or parameter 103,
Motor Voltage, after motor
current has been entered in parameter 105 can
automatically change the value in parameter 105.
105
Motor Current
(MOTOR CURRENT)
Value:
0.01 to drive rating
★
Set based on motor nameplate.
Function:
The rated motor current in amps is used for setting output current and
providing motor thermal protection. It is important to set the motor
current to the full load current rating (FLA) of the motor.
Description of choice:
Set a value that equals the nameplate data on the motor.