![background image](http://html1.mh-extra.com/html/danfoss/vlt-6002-6011/vlt-6002-6011_installation-operation-and-maintenance-manual_3482230095.webp)
95
Freeze Output (FRZ.OUT.)
The ouput frequency has been frozen.
DANGER
!
When in
Freeze Output Request, motor may re-
start at any time without warning.
Freeze Output Request (FRZ.REQ.)
A start command has been given, but the motor will remain stopped
until a Run Permission signal is received via a digital input.
Reversing and Start (START F/R)
Reversing and start 2 on terminal 19, parameter 303, Digital Inputs;
and Start on terminal 18, parameter 302, Digital Inputs are enabled at
the same time. The motor will remain stopped until one of the signals
becomes a logic ‘0’.
Automatic Motor Adaptation Running (AMA RUN)
Automatic motor adaptation has been enabled in parameter 107,
Automatic Motor Adaptation, AMA.
Automatic Motor Adaptation Completed (AMA STOP)
Automatic motor adaptation has been completed. The drive is now
ready for operation after the Reset signal has been given. Note that the
motor will start after the drive has received the Reset signal.
Stand by (STANDBY)
The drive is able to start the motor when a start command is received.
Stop (STOP)
The motor has been stopped via a stop signal from serial communica-
tion.
DC stop (DC STOP)
The DC brake in parameter 114 through 116 has been enabled.
Drive Ready (UN. READY)
The drive is ready for operation, but terminal 27 is a logic ‘0’ and/or a
Coasting Command has been received via the serial communication.
Control Ready (CTR.READY)
This status is only active when a Profibus option card is installed.
Not Ready (NOT READY)
The drive is not ready for operation, because of a trip or because
OFF1, OFF2 or OFF3 is a logic ‘0’.
Start Inhibited (START IN.)
This status will only be displayed if, in parameter 599, Profidrive [1] has
been selected and OFF2 or OFF3 is a logic ‘0’.
Exceptions XXXX
The microprocessor of the control has stopped and the drive is not
operating. The cause may be noise on the power line, motor leads or
control wires.