Start
(START)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
★
Logic or (LOGIC OR)
[3]
Function:
See the functional description under parameter 503 Coasting.
Description of choice:
The table below shows when the motor has stopped and gives the
situations in which the drive has a start command when Digital input,
Serial communication, Logic and or Logic or has been selected.
504
DC Brake
(DC BRAKE)
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
★
Logic or (LOGIC OR)
[3]
Function:
See the functional description under parameter 503, Coasting.
Description of choice:
The table below shows when the motor is running and is DC-braking
when Digital input, Serial communication, Logic and or Logic or has
been selected.
NOTE
DC braking inverse, through terminals 19 and
27, and bit 03 of the control word, is active when
logic 0 is selected.
Digital Input
Serial Communication
Term.
Serial
Term.
Serial
19/27
Comm.
Function
19/27
Comm.
Function
0
0
DC brake
0
0
DC brake
0
1
DC brake
0
1
Motor run
1
0
Motor run
1
0
DC brake
1
1
Motor run
1
1
Motor run
Logic and
Logic or
Term.
Serial
Term.
Serial
19/27
Comm.
Function
19/27
Comm.
Function
0
0
DC brake
0
0
DC brake
0
1
Motor run
0
1
DC brake
1
0
Motor run
1
0
DC brake
1
1
Motor run
1
1
Motor run
Digital Input
Serial Communication
Serial
Serial
Term. 18 Comm.
Function
Term. 18 Comm.
Function
0
0
Stop
0
0
Stop
0
1
Stop
0
1
Start
1
0
Start
1
0
Stop
1
1
Start
1
1
Stop
Logic and
Logic or
Serial
Serial
Term. 18 Comm.
Function
Term. 18 Comm.
Function
0
0
Stop
0
0
Stop
0
1
Stop
0
1
Start
1
0
Stop
1
0
Start
1
1
Start
1
1
Start
✭
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.