Compact, Mains supply 3 x 525 - 600 V
According to international requirements
VLT type 5016
5022
5027
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (550 V)
23
28
34
I
VLT, MAX
(60 s) [A] (550 V)
25
31
37
I
VLT,N
[A] (575 V)
22
27
32
I
VLT, MAX
(60 s) [A] (575 V)
24
30
35
Output
S
VLT,N
[kVA] (550 V)
22
27
32
S
VLT,N
[kVA] (575 V)
22
27
32
Typical shaft output
P
VLT,N
[kW]
15
18.5
22
Typical shaft output
P
VLT,N
[HP]
20
25
30
High overload torque (160 %):
Output current
I
VLT,N
[A] (550 V)
18
23
28
I
VLT, MAX
(60 s) [A] (550 V)
29
37
45
I
VLT,N
[A] (575 V)
17
22
27
I
VLT, MAX
(60 s) [A] (575 V)
27
35
43
Output
S
VLT,N
[kVA] (550 V)
17
22
27
S
VLT,N
[kVA] (575 V)
17
22
27
Typical shaft output
P
VLT,N
[kW]
11
15
18.5
Typical shaft output
P
VLT,N
[HP]
15
20
25
Max. cable cross-section to motor,
16
16
35
brake and loadsharing [mm
2
]/[AWG]
2)
6
6
2
Min. cable cross-section to motor,
0.5
0.5
10
brake and loadsharing [mm2]/[AWG]
4)
20
20
8
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (550 V)
22
27
33
I
L,N
[A] (600 V)
21
25
30
High overload torque (160 %):
Rated input current
I
L,N
[A] (550 V)
18
22
27
I
L,N
[A] (600 V)
16
21
25
Max. cable cross-section,
16
16
35
power [mm
2
]/[AWG]
2)
6
6
2
Max. pre-fuses
[-]/UL
1)
[A]
30
35
45
Efficiency
3)
0.96
0.96
0.96
Weight IP 20 EB
[kg]
23
23
30
Power loss at max. load
[W]
576
707
838
Enclosure
IP 20 / Nema 1
1. For type of fuse see section
Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply
with national and local regulations on min. cable cross-section.
VLT
®
5000 Design Guide
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark
49
Technical dat
a