Bookstyle and Compact, Mains supply 3 x 380 - 500 V
According to international requirements
VLT type 5005
5006
5008
5011
Output current
I
VLT,N
[A] (380-415 V)
7.2
10
13
16
I
VLT, MAX
(60 s) [A] (380-415 V)
11.5
16
20.8
25.6
I
VLT,N
[A] (440-500 V)
6.3
8.2
11
14.5
I
VLT, MAX
(60 s) [A] (440-500 V)
10.1
13.1
17.6
23.2
Output
S
VLT,N
[kVA] (380-415 V)
5.5
7.6
9.9
12.2
S
VLT,N
[kVA] (440-500 V)
5.5
7.1
9.5
12.6
Typical shaft output
P
VLT,N
[kW]
3.0
4.0
5.5
7.5
Typical shaft output
P
VLT,N
[HP]
4
5
7.5
10
Max. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2
)
4/10
4/10
4/10
4/10
Rated input current
I
L,N
[A] (380 V)
7
9.1
12.2
15.0
I
L,N
[A] (460 V)
6
8.3
10.6
14.0
Max. cable cross-section power [mm
2
]/[AWG]
2)
4/10
4/10
4/10
4/10
Max. pre-fuses [-]/UL
1)
[A]
16/15
25/20
25/25
35/30
Efficiency
3)
0.96
0.96
0.96
0.96
Weight IP 20 EB Bookstyle [kg]
7.5
9.5
9.5
9.5
Weight IP 20 EB Compact [kg]
8.5
10.5
10.5
10.5
Weight IP 54 EB Compact [kg]
12
14
14
14
Power loss at max. load.
[W]
139
198
250
295
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.