General technical data
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units
3 x 200/208/220/230/240 V ±10%
Supply voltage 380-500 V units
3 x 380/400/415/440/460/500 V ±10%
Supply voltage 525-600 V units
3 x 525/550/575/600 V ±10%
Supply voltage 525-690 V units
3 x 525/550/575/600/690 V ±10%
Supply frequency
48-62 Hz +/- 1 %
See the section on special conditions in the Design Guide
Max imbalance of supply voltage:
VLT 5001-5011, 380-500 V and 525-600 V and VLT 5001-5006, 200-240 V
±2.0% of rated supply voltage
VLT 5016-5062, 380-500 V and 525-600 V and VLT 5008-5027, 200-240 V
±1.5% of rated supply voltage
VLT 5072-5552, 380-500 V and VLT 5032-5052, 200-240 V
±3.0% of rated supply voltage
VLT 5042-5602, 525-690 V
±3.0% of rated supply voltage
True Power factor (
λ
)
0.90 nominal at rated load
Displacement Power Factor (cos
φ
)
near unity (>0.98)
No. of switchings on supply input L1, L2, L3
approx. 1 time/min.
See the section on special conditions in the Design Guide
VLT output data (U, V, W):
Output voltage
0-100% of supply voltage
Output frequency VLT 5001-5027, 200-240 V
0-132 Hz, 0-1000 Hz
Output frequency VLT 5032-5052, 200-240 V
0-132 Hz, 0-450 Hz
Output frequency VLT 5001-5052, 380-500 V
0-132 Hz, 0-1000 Hz
Output frequency VLT 5062-5302, 380-500 V
0-132 Hz, 0-450 Hz
Output frequency VLT 5352-5552, 380-500 V
0-132 Hz, 0-300 Hz
Output frequency VLT 5001-5011, 525-600 V
0-132 Hz, 0-700 Hz
Output frequency VLT 5016-5052, 525-600 V
0-132 Hz, 0-1000 Hz
Output frequency VLT 5062, 525-600 V
0-132 Hz, 0-450 Hz
Output frequency VLT 5042-5302, 525-690 V
0-132 Hz, 0-200 Hz
Output frequency VLT 5352-5602, 525-690 V
0-132 Hz, 0-150 Hz
Rated motor voltage, 200-240 V units
200/208/220/230/240 V
Rated motor voltage, 380-500 V units
380/400/415/440/460/480/500 V
Rated motor voltage, 525-600 V units
525/550/575 V
Rated motor voltage, 525-690 V units
525/550/575/690 V
Rated motor frequency
50/60 Hz
Switching on output
Unlimited
Ramp times
0.05-3600 sec.
Torque characteristics:
Starting torque, VLT 5001-5027, 200-240 V and VLT 5001-5552, 380-500 V
160% for 1 min.
Starting torque, VLT 5032-5052, 200-240 V
150% for 1 min.
Starting torque, VLT 5001-5062, 525-600 V
160% for 1 min.
Starting torque, VLT 5042-5602, 525-690 V
160% for 1 min.
Starting torque
180% for 0.5 sec.
Acceleration torque
100%
Overload torque, VLT 5001-5027, 200-240 V and VLT 5001-5552, 380-500 V,
VLT 5001-5062, 525-600 V, and VLT 5042-5602, 525-690 V
160%
Overload torque, VLT 5032-5052, 200-240 V
150%
Arresting torque at 0 rpm (closed loop)
100%
The torque characteristics given are for the frequency converter at the high overload torque level (160%). At the
normal overload torque (110%), the values are lower.