PNU
#
Parameter description
Factory setting
Range
Changes
during
operation 4-Setup
Conversion
index
Data type
700
Relay 6, function
Ready signal
Yes
Yes
0
5
701
Relay 6, ON delay
0 sec.
0.00-600 sec.
Yes
Yes
-2
6
702
Relay 6, OFF delay
0 sec.
0.00-600 sec.
Yes
Yes
-2
6
703
Relay 7, function
Motor running
Yes
Yes
0
5
704
Relay 7, ON delay
0 sec.
0.00-600 sec.
Yes
Yes
-2
6
705
Relay 7, OFF delay
0 sec.
0.00-600 sec.
Yes
Yes
-2
6
706
Relay 8, function
Mains ON
Yes
Yes
0
5
707
Relay 8, ON delay
0 sec.
0.00-600 sec.
Yes
Yes
-2
6
708
Relay 8, OFF delay
0 sec.
0.00-600 sec.
Yes
Yes
-2
6
709
Relay 9, function
Fault
Yes
Yes
0
5
710
Relay 9, ON delay
0 sec.
0.00-600 sec.
Yes
Yes
-2
6
711
Relay 9, OFF delay
0 sec.
0.00-600 sec.
Yes
Yes
-2
6
VLT
®
5000 Design Guide
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark
139
Factory sett
ings